Cleaning Program Increases Electric Power General in a Geothermal Plant

Story Image

Situation

A Geothermal Power Plant experiment operating problem due to the chemical and biological oxidation of sulfides in the geothermal condensate. Serious rhombic sulfur fouling occurred, both in lines and fill of the cooling tower and barometric condensers, causing loss of condenser vacuum and therefore electric power generation losses in both units.

Rhombic sulfur fouling concentration amounted to more than 94%, which is highly difficult to remove online.

The first unit, with initial capacity to produce 26.8 Mw, was producing only ~19.5 Mw. When the unit was taken offline, serious sulfur fouling was found in its condenser fill.

Story Image

Solution

By laboratory tests, Nalco Water designed and developed a cleaning solution composed of emollients, wetting agents, solubilizers and highly powerful complexing agents. 

The sulfur deposits were eliminated by solubilizing their supporting salts and breaking down the sulfur macro crystals, using a highly alkaline solution developed by Nalco Water.

Story Image

Results

As a result of the chemical cleaning program recommended and advised by Nalco Water, the unit reported a three-Mw/Hr increase in electric power generation per unit once placed back in operation.

Likewise, in a joint operation of the geothermal power plant, the vacuum pumps were cleaned and repaired, and the cooling tower film type fill was changed to a hybrid type fill. This enabled the power plant to bring the unit up to nearly 27-Mw of generation, thus eliminating the derating completely.

Story Image
eROI Logo
Annual Savings
Operational Performance
980,000
Value Delivered
View definition
Energy
24.48 Millionkwh

Related Success Stories

Partnering with customers to solve their greatest challenges.

Nalco Water RRA™ Technology Helps Alumina Customer Save Water and Improve Profitability

Nalco Water introduced a proprietary emulsion flocculant, called RRA™, to enhance the handling of red mud tailings. ...

Amine Performance Provides Gas Plant Real-time Information Results in Operational Efficiency Improvements

Nalco Water’s OMNI Amine Performance Monitor was installed to help determine the reason for this plant’s high usage. One...

This partnership is the whole package

Nalco Water implemented 3D TRASAR™ Water Management Technology to help the turbine condenser operate more efficiently. A...

West Coast Refinery Reduces Water Consumption in Drought-Stricken Region

Using its Best Practices Gap Analysis, Nalco Water identified the refinery’s boiler system as a potential reliability ri...

Water Savings for ADM Ethanol Facility

Ecolab’s CIP technology and associated chemistries led to more consistent fermentation and enhanced system performance a...

Using Digital Insights to Help Reduce Hospital Infection Rates

Proper hand hygiene helps everyone stay healthy in daily life....

New 3D TRASAR™ Technology for Desalter Brine Improves System Assurance and Helps Optimize Tramp Amine Removal

Robust monitoring & control achieves consistent performance without compromising asset reliability. ...

Innovative Field Test Allows Refiner to Manage Risks Posed by Crudes Contaminated with Tramp Amines

PATHFINDER™ Amine Test provides an added layer of protection from tramp amines....

Best Practices for Tramp Amine Contaminated Crude Improves Crude Flexibility

Providing crude flexibility while mitigating tramp amine risks. XX Discountinued...

How 3DTRASAR for Pulp Wash Delivers Consistently Clean Pulp

Discover how data driven 3DTRASAR for Pulp Wash improves washing performance, supports process consistency, and helps mi...

Helping Save Water and Improve Operations in Texas

Austin, Texas plant produces chips that go into mobile devices. Ecolab 3D TRASAR™ Technology has helped the plant dramat...

Wrapping Up Savings in Papermaking

Read how a pulp and paper company implemented PARETO Mixing Technology to save $95,000 per year....